Merlin Gerlin Circuit Breaker Compact NS100N TM100D
Merlin Gerlin Circuit Breaker Compact NS100N TM100D
Stock: 22
Couldn't load pickup availability
Product description and type information
Merlin Gerin Compact NS100N Circuit Breaker with TM100D Trip Unit Specifications:
- Product Type: Molded Case Circuit Breaker (MCCB)
- Manufacturer: Schneider Electric (Merlin Gerin brand)
- Model: Compact NS100N with TM100D
- Device Application: Distribution protection
- Poles Description: 3P 3d (3 poles, 3 protected)
- Rated Current (In): 100 A at 40 °C
- Trip Unit Name: TM100D
- Trip Unit Technology: Thermal-Magnetic
- Trip Unit Rating: 80–100 A (adjustable)
-
Protection Type:
- Long-time overload protection (thermal)
- Instantaneous short-circuit protection (magnetic)
- Rated Insulation Voltage (Ui): 750 V AC 50/60 Hz (IEC 60947-2)
- Rated Impulse Withstand Voltage (Uimp): 8 kV (IEC 60947-2)
- Rated Operational Voltage (Ue): 690 V AC 50/60 Hz (IEC 60947-2)
- Network Type: AC
- Network Frequency: 50/60 Hz
- Breaking Capacity Code: N
- Breaking Capacity (Icu):
-
Rated Service Breaking Capacity (Ics):
- 85 kA at 220/240 V AC 50/60 Hz
- 25 kA at 380/415 V AC 50/60 Hz
- 20 kA at 440 V AC 50/60 Hz
- 15 kA at 500/525 V AC 50/60 Hz
- 8 kA at 660/690 V AC 50/60 Hz
- Suitability for Isolation: Yes (IEC 60947-2)
- Utilization Category: Category A
- Control Type: Toggle
- Mounting Mode: Fixed
- Mounting Support: Backplate
- Mounting Position: Horizontal, vertical, or flat on the back
- Connection Type: Bolt-on (front connection, upside and downside)
- Connection Pitch: 35 mm
- Long-Time Pick-Up Adjustment Type (Ir): Adjustable (thermal)
- Long-Time Pick-Up Adjustment Range: 0.8–1 x In (80–100 A)
- Long-Time Protection Delay: Fixed (thermal curve)
- Instantaneous Pick-Up Adjustment Type (Im): Fixed (magnetic)
- Instantaneous Pick-Up Adjustment Range: 800 A
- Mechanical Durability: 50,000 cycles
-
Electrical Durability:
- 50,000 cycles at 440 V In/2
- 25,000 cycles at 440 V In
- 10,000 cycles at 690 V In
- IP Degree of Protection: IP40 (IEC 60529)
- IK Degree of Protection: IK07 (IEC 62262)
- Electrical Shock Protection Class: Class II (front face)
- Pollution Degree: 3 (IEC 60664-1)
- Ambient Air Temperature for Operation: -25 to 70 °C
- Ambient Air Temperature for Storage: -50 to 85 °C
- Relative Humidity: 0–95 %
- Operating Altitude: 0–2000 m without derating; 2000–5000 m with derating
- Standards Compliance: IEC 60947-2, UL 508, CSA C22.2, CCC, EAC
- Product Certifications: IEC, UL, CSA, CCC, EAC
-
Dimensions:
- Width: 105 mm (3P), 140 mm (4P)
- Height: 161 mm
- Depth: 86 mm
- Weight: Approximately 2.2 kg
- HS Code: 8536.20.90
- Country of Origin: France
SKU:CE-07-07-01-6152426582593
12 Months Warranty
12 Months Warranty
All our items are thoroughly tested by our in house professionals to ensure they are safe and reliable. This allows us to confidently offer a 12 month warranty on every product.
Order Today = Shipped Today
Order Today = Shipped Today
Place your order before 16:00 CET and we’ll ship it the same day for fast and reliable delivery.
Over 15.000 Satisfied Customers
Over 15.000 Satisfied Customers
Tens of thousands of customers have trusted us with their orders. Have a question or need advice? Our team is always happy to help!
Delivery & Returns
Delivery & Returns
1. Normal delivery the next business day (The Netherlands). Other countries may take longer, sometimes you have to wait a little longer to get your order, but it's always worth it!
2. Returns, email or call for your RMA number, without RMA number we can not provide a Refund.
Why buy from us
Why buy from us
How we stand out:
1. We are a 100% Dutch company with a warehouse in The Netherlands.
2. In stock means really IN STOCK.
3. All Used Industrial Parts are inspected before listing for sale.
4. All Used Industrial Parts come with a DOA warranty and a 6 months warranty.
5. The Biggest inventory! We buy (and sell) "Surplus New", "Used" and "Obsolete" Automation Controls, and Industrial Process Equipment daily, so we are proud of our huge inventory!
Share

More info
View all-
Wilo PARA 25‑130/9‑87/SC Circulation Pump: High...
Modern heating and cooling systems rely on circulation pumps to move water efficiently through boilers, radiators or underfloor loops. An effective pump not only keeps your home or industrial process...
Wilo PARA 25‑130/9‑87/SC Circulation Pump: High...
Modern heating and cooling systems rely on circulation pumps to move water efficiently through boilers, radiators or underfloor loops. An effective pump not only keeps your home or industrial process...
-
Parker Brand Overview: Precision and Reliabilit...
Parker Brand Overview: Precision and Reliability in Hydraulics and Pneumatics Parker Hannifin is a global leader in motion and control technologies.Known for its broad portfolio of hydraulic components, pneumatic fittings...
Parker Brand Overview: Precision and Reliabilit...
Parker Brand Overview: Precision and Reliability in Hydraulics and Pneumatics Parker Hannifin is a global leader in motion and control technologies.Known for its broad portfolio of hydraulic components, pneumatic fittings...
-
B&R and ABB PLCs: Flexible Control Solutions fo...
Programmable logic controllers (PLCs) are the backbone of modern automation. These robust devices coordinate sensors, actuators and communication networks so factories, process plants and utilities run safely and efficiently. While...
B&R and ABB PLCs: Flexible Control Solutions fo...
Programmable logic controllers (PLCs) are the backbone of modern automation. These robust devices coordinate sensors, actuators and communication networks so factories, process plants and utilities run safely and efficiently. While...